PLCs on the internet: five immediate steps after the 2026 attacks

Since April, US agencies have been warning about targeted attacks on internet-reachable controllers. What is behind it and what you can implement within a week.

The situation

On 7 April 2026, the FBI, CISA, NSA, EPA, DOE and US Cyber Command published a joint warning. Attackers targeted internet-exposed PLCs, mainly Rockwell Automation/Allen-Bradley. They altered project files and manipulated what HMI and SCADA screens displayed. Later reports also mention Schneider Electric Modicon M340 and Siemens S7-1200.

Five immediate steps

  1. Check the outside view: which ports on your public IP addresses answer? Industrial protocols such as 102 (S7), 502 (Modbus) or 44818 (EtherNet/IP) never belong on the internet.
  2. Consolidate remote access: one entry point via VPN or jump host with multi-factor login. Switch off direct port forwards.
  3. Enable write protection: many controllers have protection levels or a mode switch. Use them.
  4. Back up project files: a current, verified backup of every PLC program, stored offline.
  5. Detect changes: a passive sensor reports write access from unknown hosts immediately.
Check yourselfOur OT port reference lists the default ports of all common industrial protocols.

The underestimated weak spot

Many of this year’s advisories do not concern the controller itself but the software around it: remote maintenance clients, firmware tools and engineering workstations. Whoever controls the workstation needs no flaw in the PLC. Treat engineering computers like servers: own zone, no email, no web browsing.

This article is for general information and is not legal advice.